A UPS box carries two numbers, such as 1500VA/900W. The VA figure is the volts times the amps it can supply, and the W figure the real power it can deliver; the ratio between them is the power factor. Converting VA to watts takes one multiplication by that factor, and watts to VA one division.
Put in a VA rating, a number of watts and the power factor, and this VA to watts converter works out both ways. Put in volts and amps, and it works out the kVA for a single-phase or three-phase supply, and the kW at your power factor. Every figure it supplies names its source, and the list of what it cannot tell you is below the answer.
In this guide
The VA to watts converter
The VA figure on a UPS's box or spec sheet, such as 1500 for a 1500VA/900W unit. For kVA, multiply by 1000: 3 kVA is 3000.
The W figure: a UPS's watt rating, or the load you want it to carry, from each device's label or the PSU calculator.
For a UPS, its watt rating divided by its VA rating: APC's BX1500M is 900 divided by 1500, which is 0.6. For a device, the figure on its spec sheet. A power factor of 1 means watts and VA are the same.
120 for a US wall outlet, 240 for a US dryer or range outlet. For three phase, use the voltage between two lines, such as 208 V, with 480 V common in factories.
The amps on the label, the circuit or a clamp meter, for the kVA lines.
Homes and offices on an ordinary wall outlet are single phase. Three phase is found in factories, data centres and some larger buildings.
How that is worked out, line by line
- kW from those volts and amps, at your power factor0.72 kW
- Current at that VA and your voltage12.50 A
- That VA in kVA1.500 kVA
- Those watts in kW0.900 kW
- VA for those watts at the 80 PLUS power factor1,000 VA
- APC BX1500M's power factor, for comparison0.60
On those numbers you are in the Over 300 W, up to 1,000 W band, which is the section below.
This runs entirely inside your browser. Nothing you type is sent anywhere, saved or read by this site, and the page keeps working with the network unplugged.
Newsletter
One email a week, and only when there is something in it
Every guide I published or rewrote that week, up to six of them, each with a line on who it is for and what it settles. No prices, no deals, nothing else.
It goes out on Thursday mornings. In a week when nothing new went up, nothing is sent.
Your address goes to MailerLite, who deliver the email, and nowhere else. Every email has an unsubscribe link. The email ends with one link to my Amazon storefront, and as an Amazon Associate I earn from qualifying purchases. Privacy policy.
Where every number here comes from
No part of this was measured on a bench here. This site works from published specifications and from what owners report, and every number below is either one you typed in or a published figure with its source named next to it.
The figures this page supplies
- The three-phase factor (the square root of 3): 1.7320. Schneider Electric's FAQ FA101600: for three phase, multiply the line-to-line voltage by the load current, then by 1.732 (the square root of 3), and divide by 1000.
- VA in a kVA, and watts in a kW: 1,000. NIST SP 811, chapter 4, Table 5: the SI prefix kilo (k) is the factor 10^3.
- APC Back-UPS Pro BX1500M's VA rating: 1,500 VA. APC's own product page: BX1500M, APC Back-UPS Pro, 1500VA/900W.
- APC Back-UPS Pro BX1500M's watt rating: 900 W. The same APC product page: 1500VA/900W.
- Power factor an 80 PLUS PC power supply must reach: 0.9000. CLEAResult's 80 PLUS program details: power supplies must be 80% efficient or better at 10, 20, 50 and 100% of rated load, with a true power factor of 0.9 or higher.
Why each step is the step it is
- Watts from that VA:
va * pf. VA times the power factor: Fluke defines power factor as working power over apparent power, so watts are the VA times it. - VA for those watts:
watts / pf. Watts divided by the power factor: the same relation the other way round. - kVA from those volts and amps:
volts * amps * phase_k / kilo + phase_ok. Volts times amps over 1000 for single phase, and times 1.732 as well for three phase: Schneider Electric's FAQ FA101600. - kW from those volts and amps, at your power factor:
kva_amps * pf. The kVA above times the power factor. Schneider's FAQ warns that leaving the power factor out undersizes a transformer, because it is always less than 1. - Current at that VA and your voltage:
va / (volts * phase_k) + phase_ok. VA divided by volts, and by 1.732 as well for three phase: the kVA formula turned round. - That VA in kVA:
va / kilo. VA divided by 1000, NIST's kilo prefix. - Those watts in kW:
w_out / kilo. The watts from the VA, divided by 1000. - VA for those watts at the 80 PLUS power factor:
watts / pfc_pf. Your watts over 0.9, the power factor the 80 PLUS label asks of a PC power supply: the VA a PC load of that many watts comes to at that power factor. - APC BX1500M's power factor, for comparison:
apc_w / apc_va. APC's 900 W rating over its 1500 VA rating for the BX1500M.
What this cannot tell you
Every calculator has an edge, and a page that hides its edge is worse than no page at all. Here is this one's.
- It is arithmetic on the figures you give it. No UPS or device was put on a meter for it, and this site has not measured what any of them draws.
- It is only as right as the power factor. A UPS's own is its watt rating over its VA rating; a device's changes with the device and how hard it is working, and a guessed figure moves every answer with it.
- A UPS has two limits, and the load has to fit under both. This page converts between them; it does not say how long a UPS will run, which the UPS runtime calculator works out.
- The three-phase line assumes a balanced load and the voltage between two lines. An unbalanced load, or a line-to-neutral voltage, needs a different sum.
- It is not electrical advice. Sizing a generator, a transformer or a new circuit is a job for a licensed electrician, who will also allow for motors and other loads that draw more as they start.
What that many watts means for a UPS
These follow from the answer above and nothing else. Each heading below covers one span of results, so read the one the calculator pointed you at and ignore the rest.
300 W or less
A light load against a UPS's watt rating. Add up the W on the label of everything you plan to plug into the battery outlets and keep the total under this figure. Keeping a router and modem running through an outage is one use for a small one; the guide below covers routers.
Best Gaming Router Under $200, 5 Honest Picks for 2026 covers this range in full.
Over 300 W, up to 1,000 W
APC rates its BX1500M, a 1500 VA tower, at 900 W, inside this band. A gaming PC working hard can need a figure in this range: the PSU calculator adds up a build's peak, and the guide below covers a full build. This site has not covered a UPS yet, so it is not going to name one.
Best 1440p Gaming PC Build $1200 Parts List (2026) covers this range in full.
More than 1,000 W
More than APC's 1500 VA tower carries, so this is a larger unit, often rated in kVA. Check the load against both of its ratings, and use the watts to amps converter for what it draws from the outlet. A new circuit is a job for a licensed electrician.
Once the load fits under both ratings, the UPS runtime calculator works out how long a battery lasts carrying it, and the watts to amps converter what it draws from the outlet. A VA to watts converter is only as right as the power factor you give it, so take it from the UPS's own two ratings or the device's spec sheet.
Questions about the VA to watts converter
How do I convert VA to watts?
Multiply the VA by the power factor. A 1500 VA rating at a power factor of 0.6 is 900 W, which is APC's own rating for its BX1500M. At a power factor of 1 the watts equal the VA, so 1500 VA is 1,500 W. For a UPS, the power factor is its watt rating over its VA rating; for a device, it is on the spec sheet. This VA to watts converter does the sum for any label.
How do I convert watts to VA?
Divide the watts by the power factor. 900 W at a power factor of 0.6 is 1,500 VA. A PC whose power supply carries the 80 PLUS label must reach a power factor of 0.9 or higher, and at 0.9 the same 900 W is 1,000 VA. Fluke defines the power factor as working power in kW over apparent power in kVA, which is why the VA figure is the larger one whenever the power factor is below 1.
How do I calculate kVA from volts and amps?
For single phase, multiply the volts by the amps and divide by 1000: 120 V at 10 A is 1.2 kVA. For three phase, multiply by 1.732 as well, using the voltage between two lines: 208 V at 100 A is 36.03 kVA. Those are Schneider Electric's formulas for sizing a transformer, and this kVA calculator works both. Multiply the kVA by the power factor for kW: 36.03 kVA at 0.9 is 32.42 kW.
How many watts is a 1,500 VA UPS?
It depends on the UPS's power factor, so read the W figure on the box. APC rates its BX1500M at 1,500 VA and 900 W, a power factor of 0.6. A 1,500 VA unit rated at a power factor of 0.9 would carry 1,350 W. In kVA, 1,500 VA is 1.5 kVA. Schneider Electric's white paper on watts and volt-amps explains why the watt figure is the one a computer's load has to fit under.
What size UPS do I need in VA?
One whose watt rating and VA rating are both at least your load's. A 500 W PC load at a power factor of 0.9, the figure the 80 PLUS label asks of a PC power supply, is 556 VA, so a 1,500 VA, 900 W UPS covers it on both counts. A 1000 W load at the same power factor is 1,111 VA, which fits under 1,500 VA, but its 1000 W does not fit under 900 W, so that UPS would not carry it. The UPS runtime calculator then works out how long a unit lasts on battery.
What is the difference between kVA and kW?
kVA is apparent power, the volts times the amps over 1000; kW is the part that does work, the kVA times the power factor. 120 V at 10 A is 1.2 kVA, and at a power factor of 0.6 that is 0.72 kW. Schneider Electric's FAQ warns that a load's power factor is always below 1, so sizing a transformer on kW without it would undersize it. This page prints both lines, so the kW figure is always beside the kVA one.
Sources
- Fluke: power factor, what it is and how to calculate it: A meter maker's explanation that power factor is working power (kW) over apparent power (kVA), and that apparent power is volts times amps.
- Schneider Electric FAQ FA101600: the formula for the kVA of a transformer: Gives kVA as volts times amps over 1000 for single phase and times 1.732 as well for three phase, and warns that a load's power factor is always below 1, so leaving it out undersizes.
- APC Back-UPS Pro BX1500M product page: The maker's rating for a common tower UPS: 1500VA/900W, which is this page's opening example.
- Schneider Electric white paper 15: Watts and Volt-Amps, Powerful Confusion: Explains why a UPS's watt rating, not its larger VA figure, is the one a computer's load has to fit under.
- CLEAResult: 80 PLUS program details: Sets the 80 PLUS requirement for computer power supplies, including a true power factor of 0.9 or higher.
- NIST SP 811, chapter 4: the two classes of SI units and the SI prefixes: Table 5 gives the kilo prefix, 10^3, behind kVA and kW.