Every wire has some resistance, so some of the voltage is lost along it before it reaches the device. On a short run it hardly matters. On a long 12 V run to an LED strip, a camera or a car accessory, a volt or two can be the difference between working and not.
Put in the supply voltage, the current the load draws, the one-way length of the run and the wire gauge, and this voltage drop calculator works out the volts lost, the share of the supply that is, and the volts left at the load. Put in the most drop you will accept, and it names the thinnest common gauge that stays within it. Every figure it supplies names its source, and the list of what it cannot tell you is below the answer.
The sum is short. A wire's resistance is copper's resistivity times its length, divided by its cross-section, and the current flows out to the load and back, so the length counts twice. Multiply that resistance by the amps and you have the volts lost, by Ohm's law. A thicker gauge, a shorter run or a higher supply voltage each brings the share down.
In this guide
The voltage drop calculator
The voltage at the start of the run: 12 for a car or a 12 V LED supply, 120 for a US outlet, 240 for a US dryer or range circuit, or the figure on the power supply's label.
The amps on the device's label, or its watts divided by the volts. The watts to amps converter works it out.
From the supply to the load, measured along the wire. The calculator counts the return wire itself, so do not double it.
Printed on the cable's jacket, such as 12 AWG or 14/2. A smaller number is a thicker wire.
20 for a cool, lightly loaded run. A wire carrying a heavy current warms up; the NEC's resistance table assumes 75.
3 is the figure the NEC's informational note recommends for a branch circuit. The gauge the calculator names keeps the drop at or under it.
How that is worked out, line by line
- Diameter of that gauge2.053 mm
- Cross-section of that gauge6,530 cmil
- The same cross-section in square millimetres3.309 mm²
- Resistance of 1,000 ft of that wire at your temperature1.5882 ohms
- Resistance of the whole run, out and back0.0794 ohms
- Smallest cross-section that keeps the drop within your limit7.299 mm²
- Drop on that recommended gauge2.62 %
- Longest run your gauge allows within your limit11 ft
- Power turned into heat in the wire7.9 W
- The run's length in metres7.6 m
On those numbers you are in the Over 5%, up to 10% band, which is the section below.
This runs entirely inside your browser. Nothing you type is sent anywhere, saved or read by this site, and the page keeps working with the network unplugged.
Newsletter
One email a week, and only when there is something in it
Every guide I published or rewrote that week, up to six of them, each with a line on who it is for and what it settles. No prices, no deals, nothing else.
It goes out on Thursday mornings. In a week when nothing new went up, nothing is sent.
Your address goes to MailerLite, who deliver the email, and nowhere else. Every email has an unsubscribe link. The email ends with one link to my Amazon storefront, and as an Amazon Associate I earn from qualifying purchases. Privacy policy.
Where every number here comes from
No part of this was measured on a bench here. This site works from published specifications and from what owners report, and every number below is either one you typed in or a published figure with its source named next to it.
The figures this page supplies
- Resistivity of annealed copper at 20 °C: 10.3710 ohm cmil/ft. The Copper Development Association's copper fact sheet: annealed copper of 100% IACS has a volume resistivity of 0.017241 ohm mm²/m at 20 °C (the IEC's 1/58), which is 10.371 ohms per circular mil foot.
- Rise in copper's resistance for each degree: 0.3930 % per °C. The same CDA fact sheet: the temperature coefficient of resistance at 20 °C for annealed copper of 100% IACS is 0.00393 (0.393% for each degree), applicable from -100 to 200 °C.
- Diameter of 36 AWG wire: 5 mils. ASTM B258 as RF Cafe's copper wire reference quotes it: by definition 36 AWG is 0.0050 inches in diameter, which is 5 mils (thousandths of an inch).
- Ratio of 4/0's diameter to 36 AWG's, over 39 gauge steps: 92. The same RF Cafe page: 0000 (4/0) is 0.4600 inches, the ratio of the two diameters is 92, and there are 39 steps between them, so each step is the 39th root of 92 (ASTM B258).
- Wires the current flows through on a two-wire run: 2. IAEI Magazine's and Mike Holt's single-phase voltage drop formula, VD = 2 x K x I x L / CM: the 2 is the current going out to the load and back.
- Millimetres in an inch: 25.4000 mm. NIST's length units page: the inch is defined as 25.4 mm.
- Metres in a foot: 0.3048 m. NIST SP 811 Appendix B.8: the foot is exactly 0.3048 m.
- Branch-circuit drop the NEC's informational note recommends: 3 %. Mike Holt's voltage drop calculations: the note to NEC 210.19(A) recommends sizing branch-circuit conductors to prevent a voltage drop of more than 3%.
- Feeder and branch circuit drop together, by the same notes: 5 %. The same page: the branch circuit and the feeder together should not exceed 5%. Holt and IAEI Magazine both say informational notes are not enforceable requirements.
Why each step is the step it is
- Diameter of that gauge:
d_mils / 1000 * in_mm. Mils are thousandths of an inch, and NIST's inch is 25.4 mm. - Cross-section of that gauge:
d_mils * d_mils. The diameter in mils squared: the gauge's area in circular mils. - The same cross-section in square millimetres:
cmil * Math.PI / 4 * (in_mm / 1000) * (in_mm / 1000). A circular mil is pi / 4 square mils, and a mil is 0.0254 mm. - Resistance of 1,000 ft of that wire at your temperature:
rho * warm / cmil * 1000. Copper's 10.371 ohm cmil/ft over the gauge's circular mils, for 1,000 feet, moved to your temperature. - Resistance of the whole run, out and back:
ohm_kft * two_wire * length_ft / 1000. The current flows to the load and back, so the wire is twice the run's length. - Volts lost in the wire:
drop_raw + pct_ok. Amps times the run's resistance, out and back: VD = 2 x K x I x L / CM. - Drop as a share of the supply:
drop_v / volts * 100. The volts lost over the supply voltage. - Volts left at the load:
volts - drop_v. The supply less the drop. - Thinnest common gauge within your limit:
26 - (Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 10)))) * 2 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 12)))) * 2 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 14)))) * 2 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 16)))) * 2 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 18)))) * 2 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 20)))) * 2 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 22)))) * 2 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 24)))) * 2 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 26)))) * 2 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 28)))) * 2 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 30)))) * 2 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 32)))) * 1 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 33)))) * 1 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 34)))) * 1 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 35)))) * 1 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 36)))) * 1 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 37)))) * 1 + Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 38)))) * 1) + atLeast(Math.min(1, Math.max(0, Math.ceil(need_cmil - c36 * Math.pow(g, 39)))), [0]). The circular mils your limit needs, compared with each common size from 26 AWG to 4/0, thinnest first: the first one that is big enough. - Smallest cross-section that keeps the drop within your limit:
need_cmil * Math.PI / 4 * (in_mm / 1000) * (in_mm / 1000). The circular mils the limit needs, in square millimetres. - Drop on that recommended gauge:
amps * rho * warm * two_wire * length_ft / (c36 * Math.pow(g, 36 - awg_need)) / volts * 100. The same sum on the recommended gauge's circular mils. It is at or under your limit. - Longest run your gauge allows within your limit:
limit_pct / 100 * volts / (amps * two_wire * ohm_kft / 1000). The limit's share of the supply over the volts lost per foot of run. - Power turned into heat in the wire:
drop_v * amps. The volts lost times the amps. - The run's length in metres:
length_ft * ft_m. Feet times NIST's 0.3048 m.
What this cannot tell you
Every calculator has an edge, and a page that hides its edge is worse than no page at all. Here is this one's.
- It is arithmetic on the figures you give it. No wire was put on a meter for it, and this site has not measured any cable.
- It is for copper at its nominal size. Aluminium, and the copper-clad aluminium sold in some cheap speaker and network cables, resist more, and stranded wire can differ slightly from the solid-wire figure.
- It works out DC resistance on a two-wire run. On AC with large conductors, 2/0 and up in Mike Holt's article, the wire's reactance adds to the drop, and three-phase circuits use a different multiplier; this page covers neither.
- It assumes the current stays the same as the voltage falls. Real loads change: a motor can draw more, a heater less, and an LED strip dims or shifts colour, so the drop at the load is an estimate.
- Wire warms up under load, and the NEC's resistance table assumes 75 °C. At the 20 °C default the volts lost come out lower than a calculator built on that table gives; put a higher temperature in the box for a busy run.
- The gauge it names is about voltage drop only. A wire must also be rated for the current it carries and protected by the right fuse or breaker, and local codes decide what building wiring may use: that is a job for a licensed electrician.
What that much drop means
These follow from the answer above and nothing else. Each heading below covers one span of results, so read the one the calculator pointed you at and ignore the rest.
3% or less
Within the 3% the NEC's informational note recommends for a branch circuit, and a small share of a low-voltage supply. The gauge in the box is enough for the drop; check that it is also rated for the current it carries.
Over 3%, up to 5%
Over the 3% the note recommends for a branch circuit on its own, but within the 5% it gives for the feeder and branch circuit together. For a low-voltage device, check its spec sheet for the lowest input voltage it works on. The next thicker gauge, or a shorter run, brings the drop down.
Over 5%, up to 10%
More than the NEC's notes recommend for building wiring, and on a 12 V run more than half a volt gone. The gauge named in the answer above keeps the drop within your limit; a shorter run or a higher supply voltage for the same watts also cuts it.
More than 10%
A large share of the supply is lost in the wire, and the device may not get the voltage it needs. Use the gauge named in the answer above, move the supply closer to the load, or send the power at a higher voltage. New mains wiring is a job for a licensed electrician.
If you know the watts but not the amps, the watts to amps converter works them out, and the Ohm's law calculator shows the same volts, amps and ohms relation for any part. A voltage drop calculator is only as right as the length and current you give it, so measure the run along the route the wire will take, and use the current the device draws at its busiest.
Two habits avoid most wiring surprises. First, put in the one-way length: the calculator already counts the return wire, so doubling it yourself doubles the drop. Second, read the gauge off the cable itself rather than the packaging, and check what the conductor is made of. Copper-clad aluminium resists more than solid copper of the same gauge, so a run built from it loses more than the figures here show.
Questions about the voltage drop calculator
How does a voltage drop calculator work?
It works out the resistance of the wire and multiplies it by the current. The current goes out to the load and back, so the length counts twice: 25 feet of 12 AWG copper is 0.079 ohms there and back at 20 °C. At 10 A that loses 0.79 V, which is 6.62% of a 12 V supply, and leaves 11.21 V at the load. This voltage drop calculator does the same sum for any gauge, length and current, and shows each line, with copper's resistance taken from the Copper Development Association's published figure.
How does a wire gauge calculator pick the wire size?
It works the same formula backwards, from the drop you will accept. Keeping 10 A over 25 feet within 3% of 12 V needs at least 7.3 mm² of copper, so the thinnest common size that clears it is 8 AWG, at a 2.62% drop. On a 120 V circuit, 15 A over 50 feet within the same 3% needs 12 AWG. This wire gauge calculator chooses only for voltage drop: the wire must also be rated for the current, and building wiring follows local code.
How much voltage drop is acceptable?
For building wiring, an informational note in the NEC recommends sizing branch-circuit conductors for a drop of no more than 3%, and no more than 5% for the feeder and branch circuit together. Mike Holt and IAEI Magazine both point out that informational notes explain; they are not enforceable requirements. For a low-voltage device there is no such note, so its spec sheet is the guide: it gives the lowest input voltage it works on. In the example above, a 6.62% drop leaves 11.21 V of the 12 V.
How do I work out voltage drop on a 12 volt run?
The same way, and low voltage is where it matters most, because each volt lost is a bigger share. 5 A over 15 feet of 18 AWG loses 0.96 V, which is 7.98% of 12 V. The same run in 14 AWG loses 0.38 V, or 3.16%, and staying within 3% takes 12 AWG. At 120 V, the same 5 A over 15 feet of 18 AWG is only 0.8% of the supply, which is why long runs are often sent at a higher voltage.
Does temperature change voltage drop?
Yes. Copper's resistance rises by 0.393% of its 20 °C value for each degree, the Copper Development Association's figure for annealed copper. At 75 °C, the temperature IAEI Magazine says the NEC's resistance table assumes, a thousand feet of 12 AWG is 1.932 ohms instead of 1.588, and the example run loses 8.05% instead of 6.62%. A wire carrying a heavy current warms itself, so for a long, busy run put a higher temperature in the box.
Sources
- Copper Development Association: Introduction to Copper, fact sheets: Gives annealed copper's volume resistivity at 20 °C as 0.017241 ohm mm²/m (100% IACS) and its temperature coefficient of resistance as 0.00393 per degree, from -100 to 200 °C.
- RF Cafe: bare solid copper wire properties and gauge conversions: Quotes ASTM B258's definition of the American Wire Gauge: 36 AWG is 0.0050 in, 4/0 is 0.4600 in, a ratio of 92 over 39 steps, each step the 39th root of 92.
- Mike Holt: voltage drop calculations, part one: Gives the single-phase formula VD = 2 x K x I x D / CM, the NEC informational notes recommending 3% for a branch circuit and 5% with the feeder, and that such notes are not enforceable.
- IAEI Magazine: voltage drop calculations: Gives the same formula, explains the 2 as the current going out and back, and says the NEC's Chapter 9 Table 8 resistances are based on 75 °C.
- NIST: SI units, length: Gives the definition of the inch as 25.4 mm.
- NIST SP 811, Appendix B.8: factors for units listed alphabetically: Lists the foot to metre factor, 3.048 E-01, among the exact factors.